Attributes
| Gtin | 5715253183626 |
|---|
Description
iC7-Automation Frequency converter,air-cooled IC7-60FA3N05-302AE20F2+AGCX+AJFX +ALDC+BAMT+BDBA+BEF1+BF20 +DAAU IP20/Open Type, Frame: FA09 3~, 380-500 V AC, 302 A EMC category: C2 category Control Panel 2.8 OPX20 Standard I/O: 4xDI, 2xDI/O, 2xAI, 1xAO, 2xRO Fieldbus protocols enabled: Modbus TCP OS7MT Other protocols enabled: Ethernet port, no protocol Functional Safety: STO, not upgradable Other options according to model code
Specifications
| Gross weight | 80.01 Kilogram |
|---|---|
| Net weight | 66.9 Kilogram |
| Volume | 253.164 Liter |
| EAN | 5715253183626 |
| Product series | +DAAU, iC7-Automation |
| Product group | IC7-60, iC7-60 |
| Product category | FA, Frequency converter,air-cooled |
| Product type | 3N, 3~ |
| Mains voltage | 05, 380-500 V AC |
| Current rating | -302A, 302 A |
| Power rating | 160, 160 kW/250 hp |
| Protection rating | E20, IP20/Open Type |
| EMC category | F2, C2 category |
| Cable entry and EMC plate | +AAST, Standard plate |
| Integrated brake chopper | +ACXX, None |
| Extra environmental protection | +AGCX, Coated boards |
| Humidity protection device | +AHXX, None |
| Integrated common-mode filter | +AIXX, None |
| Mains input device | +AJFX, AC fuses |
| DC terminals | +ALDC, Yes |
| Touch protection | +AMXX, None |
| Heat sink access panel | +APXX, None |
| Communication interface, X1/X2 | +BAMT, Modbus TCP OS7MT |
| Communication interface, X0 | +BBEL, Ethernet port, no protocol |
| Standard I/O | +BDBA, 4xDI, 2xDI/O, 2xAI, 1xAO, 2xRO |
| Functional safety | +BEF1, STO, not upgradable |
| Control panel | +BF20, Control Panel 2.8 OPX20 |
| Interface board | +BISR, MicroSD card reader and RTC |
| Option slot A | +CAX0, None |
| Option slot B | +CBXX, None, not upgradable |
| Option slot C | +CCX0, None |
| Option slot D | +CDX0, None |
| Option Slot E | +CEX0, None |
| Customer specific application | +DBXX, None |
| Additional drive features 1 | +DD1X, None |
| Additional drive features 2 | +DE2X, None |
| Additional drive features 3 | +DF3X, None |
| Additional drive features 4 | +DG4X, None |
| Additional drive features 5 | +DH5X, None |
| High speed enabled | +DI6X, No |
| Customization file package ID | +EAXXXXXX, No customization |
| Product software ID | +ECXXX, Latest released version |
| Technical documentation | +EGIN, Installation guide |
| Customer-specific label | +EJXX, None |
| Language package | +EL01, Global |
| Product specific marine cert. | +VBXX, None |
| Frame designation | FA09, FA09 |
| Control Board type | A5E, Advanced Ethernet A5E |
| Modelcode01 | IC7-60FA3N05-302AE20F2 |
| Modelcode02 | +AGCX+AJFX |
| Modelcode03 | +ALDC+BAMT+BDBA |
| Modelcode04 | +BEF1+BF20 |
| Modelcode05 | +DAAU |
| Input Voltage | 3x380-500V, 3x380-500V |
| Input frequency | 50/60Hz, 50/60Hz |
| Short circuit current rating | 100kA, 100kA |
| Output frequency | 0-590Hz, 0-590Hz |
| Typical motor power PL (110%) | 160kW(400V)/250HP(460V), 160kW(400V)/250HP(460V) |
| Continous current IL (1/10min) | 302/302A, 302/302A |
| Overload current IL (1/10min) | 332/332A, 332/332A |
| Input current LO (1/10 min) | 291/291A, 291/291A |
| Ambient temp LO (1/10 min) | 40°C/104°F, 40°C/104°F |
| Typical motor power PH (150%) | 132KW(400V)/200HP(460V), 132KW(400V)/200HP(460V) |
| Continous current IH (1/10min) | 245/240A, 245/240A |
| Overload current IH (1/10min) | 368/360A, 368/360A |
| Input current HO (1/10 min) | 236/231A, 236/231A |
| Ambient temp HO (1/10 min) | 45°C/113°F, 45°C/113°F |
| Typical motor power PH2 (150%) | 110kW(400V)/150HP(460V), 110kW(400V)/150HP(460V) |
| Continous current IH (1/5min) | 206/196A, 206/196A |
| Overload current IH (1/5min) | 309/294A, 309/294A |
| Input curent HO2 (1/5 min) | 198/189A, 198/189A |
| Ambient temp HO2 (1/5 min) | 45°C/113°F, 45°C/113°F |
| Efficiency class-Relative loss | IE2 - 1.93%, IE2 - 1.93% |
| Maximum Power Loss LO [W] | 3438, 3438 |
| Main unit Width | 250 mm / 9.8 in, 250 mm / 9.8 in |
| Main unit Height | 909 mm / 35.8 in, 909 mm / 35.8 in |
| Main unit Depth | 370 mm / 14.6 in, 370 mm / 14.6 in |
| Calculated Net Weight [kg] | 66.9 |
| Calculated Gross Weight [kg] | 80.01 |
| ECCN EU | Y901, Y901 |
| ECCN US | 3A999.a, 3A999.a |
| Ambient temp. high overload | 45°C/113°F, 45°C/113°F |
| Ambient temp. normal overload | 40°C/104°F, 40°C/104°F |
| Enclosure rating | IP20 / OPEN TYPE, IP20 / OPEN TYPE |
| Help Counter | 1 |
| High Speed Drive Warning | NONE, NONE |
| Input current in High Overload | 236/231A, 236/231A |
| Input current in Normal Overlo | 291/291A, 291/291A |
| Product Catalog | NO_VIEW, NO VIEW |
| Product View (Switch) | GLBL, Global (Standard) |
| Recommended Plant | ERR01, ERR01 |
| Typecode Part 1 | 7FC-AUFA3N05-302AE20F2 |
| Typecode Part 2 | -000085214 |
| Vendor | ERR01, Cannot Determine Vendor |
PDF Documents
Connecting to iC7 Series Remotely via Mobile Network
Open PDF
iC7 Series Industry; Software version 26A
Open PDF
iC7-Automation Use-of DC Connections
Open PDF
MyDrive Insight for iC7; SW 2.20.0
Open PDF
MyDrive Insight Logic Feature
Open PDF
Simulation with iC7 Virtual Industry Application Guide
Open PDF
iC7-Automation Selection Guide
Open PDF
iC7-Automation Selection Guide - US English
Open PDF
iC7-Automation Frequency Converters
Open PDF
iC7 Series Control Panel
Open PDF